AMERICAN made OIL CHILLER, oil CHILLER knowledge DEPOT, AMERICAN made oil CHILLERS, cold as a ARTIC CHILL oil chillers, WATER CHILLER, better than a COOLING TOWER AMERICAN MADE Hydraulic oil CHILLER does oil & water temp have you in a TURMOIL, WASTER & OIL CHILLER AMERICAN MADE CHILLER, IS OIL CHILLER AND WATER CHILLER AMERICAN MADE AT water chiller knowledge DEPOT  QUALITY AMERICAN MADE CHILLER OIL COOLING AMERICAN WAY

 

 

HOME
About Us
Contact Us
Products
Download Specs
Chiller University
Drycleaners Page
Custom Pics
Sizing Formulas
Newsletter
Quote Form (pdf)
Hydraulic Cooling

   NASHVILLE

JEFFERSONVILLE

     

 

 

	OTHER FORMULAS FOR SIZING A COOLING UNIT										

		IT IS RECOMMENDED TO SIZE CHILLER SLIGHTLY LARGER THAN LOAD.	
FOR WATER: BTU=DELTA T X GPM X 500											

	EXAMPLE: WATER COMING IN TO UNIT IS 70 DEG F. LEAVING WATER TEMP IS 85 DEG F.										
		FLOW RATE IS 10 GPM. 									
		THE LEAVING WATER TEMP MINUS THE ENTERING WATER TEMP IS THE DELTA T.									
		85 - 70 = 15     15 X 10 X 500 = 75,000 BTU/HR (TO MAINTAIN CURRENT TEMP) 									

FOR OIL THE FORMULAS ARE VERY SIMILAR. IF THE OIL IS DTE 24 OR EQUIVALENT THE FORMULA											
	IS DELTA T X GPM X 243 = BTU/HR.										

	EXAMPLE: OIL IN RESERVOIR IS 120 DEG F. OIL RETURNING TO RESERVOIR IS 140 DEG F. 										
		FLOW RATE IS 18 GPM.								
		140-120 = 20      20 X 18 X 243 = 87,480 BTU/HR (FOR DTE 24)								

IF THE OIL DIFFERS FROM DTE 24, USE BTU = DELTA T X GPM X 500 X SPECIFIC HEAT OF FLUID										

	EXAMPLE: SAE 40 OIL HAS A SPECIFIC HEAT OF .5  									
		RESERVOIR TEMP IS 100 DEG F. RETURN OIL TEMP IS 120 DEG F. OIL FLOW 								
		RATE IS 15 GPM.								
		120 - 100 = 20      20 X 15 X 500 X .5 = 75,000 BTU/HR								

	BELOW IS A CHILLER SELECTION CHART WHEN ACTUAL BTU HEAT LOAD IS KNOWN									
										
				BTU/HR		CHILLER MODEL	TONNAGE		
				9,000		RC-0.75		0.75		
				12,000		RC-1		1.00		
				18,000		RC-1.5		1.50		
				24,000		RC-2		2.00			
				36,000		RC-3		3.00			
				48,000		RC-4		4.00			
				60,000		RC-5		5.00			
				90,000		RC-7.5		7.50			
				120,000		RC-10		10.00			
				144,000		RC-12		12.00			


	HOW TO USE THIS CHART:										
		CHOOSE THE BTU (IN RED) FROM THE CHART THAT IS EQUAL TO OR GREATER THAN									
		YOUR CALCULATED BTU HEAT LOAD. FOLLOW THE CHART TO THE RIGHT TO DETERMINE									
		THE PROPER CHILLER MODEL AND TONNAGE YOUR SYSTEM REQUIRES.									
	NOTE: MAXIMUM ENTERING FLUID TEMPERATURE IS 140 DEG F.										
											
IF YOU HAVE ANY QUESTIONS OR TROUBLE CHOOSING A CHILLER UNIT, FILL OUT A CHILLER MFG.											
QUOTE FORM WITH AS MUCH DATA AS POSSIBLE AND FAX TO 812-285-5508 OR CALL 800-334-2665											
TO REACH RYAN AT EXT 209 OR CARTER AT EXT 206											
											

Sizing chart 3

Copyright Chiller mfg. 2004